Product name: Online Low Frequency UPS Three phase
Model: BGL160KL/BGL200KL/BGL300KL/BGL400KL/BGL500KL
Rating: 160kVA-500kVA
Key features:
Rating: 160kVA-500kVA
Key features:
Input power factor > 0.99, THDi < 3%
DSP digital control technology
True online double conversion technology
Three phase in and three phase out
With isolated transformer at output
IGBT inverter design
Zero transfer time
With SPWN –sine wave pulse width modulation
Generator compatible
Cold start feature (DC power on)
Automatically charging in OFF mode
Lighting and surge protections
Short-circuit and overload protections
EMI/RFI noise filter available
Extendable battery pack
Intelligent slot interface(SNMP optional)
Application
Servers, big Data centers, Critical network devices, computer rooms, banks,medical equipment, ISP, tele-communications
Technical specification
Model |
BGL160KL |
BGL200KL |
BGL300KL |
BGL400KL |
BGL500KL | |||||
Rated Power (VA) |
160kVA |
200kVA |
300kVA |
400kVA |
500kVA | |||||
INPUT |
| |||||||||
Rated voltage |
380 V / 400 V / 415 Vac | |||||||||
Voltage range |
346 V ~ 456 V (full load)
304 V~346 V (power derating 10%) | |||||||||
Rated frequency |
50 / 60 Hz | |||||||||
Frequency range |
50 / 60 Hz ±5 Hz | |||||||||
Power factor |
≥ 0.99 | |||||||||
THDI) |
≤ 3% | |||||||||
Bypass voltage range |
± 20% | |||||||||
ECO voltage range |
± 10% | |||||||||
OUTPUT |
| |||||||||
Rated voltage |
380 V / 400 V / 415 Vac | |||||||||
Voltage regulation |
± 1% | |||||||||
Frequency |
Synchronized with utility in AC mode; 50 / 60 Hz ±0.1% in battery mode | |||||||||
Waveform |
Sinusoidal | |||||||||
Crest factor |
3:1 | |||||||||
(THDV) |
≤1% (linear load);≤5% (non-linear load) | |||||||||
Transfer time |
Mains mode to battery mode: 0 ms
Inverter mode to bypass mode: 0 ms
Inverter mode to ECO mode: 5 ~ 10 ms | |||||||||
Inverter overload capability |
102%~110%: transfer to bypass in 5 mins;
110%~125%: transfer to bypass in 1 min;
125%~150%: transfer to bypass in 30 s;
150%~200%: transfer to bypass in 200 ms;
>200%: power off in 100 ms | |||||||||
Bypass overload capability |
≤ 150%: long time running
150% < load < 200%: power off in 1 min
> 200%: power off in 100ms | |||||||||
BATTERIES |
| |||||||||
DC voltage |
600 V (12 V × 50 pcs) | |||||||||
SYSTEM |
| |||||||||
Efficiency |
Working mode ≥93%,ECO mode ≥98% | |||||||||
Alarm |
Battery mode, low battery, fans fault etc | |||||||||
Surge protection |
IEC60664-1 | |||||||||
Insulation resistance |
> 2MΩ (500Vdc) | |||||||||
Dielectric strength |
2820 Vdc, no arc in 1 min | |||||||||
IP rating |
IP 20 | |||||||||
EMI |
EN62040-2 | |||||||||
EMS |
IEC61000-4-2 (ESD) | |||||||||
|
IEC61000-4-3 (RS) | |||||||||
|
IEC61000-4-4 (EFT) | |||||||||
|
IEC61000-4-5 (surge) | |||||||||
COMMUNICATIONS |
| |||||||||
RS232,RS485,dry contacts |
Supports Windows® 98 / 2000 / 2003 / XP / Vista / 2008 / 7 / 8 / 10 | |||||||||
SNMP (optional) |
Power management from SNMP manager and web browser | |||||||||
OTHERS |
| |||||||||
Humidity |
0 ~ 95% RH @ 0 ~ 40℃ (non-condensing) | |||||||||
Noise level |
60 dB |
65 dB |
70 dB |
75 dB | ||||||
Dimensions (W×D×H) (mm) |
800 × 860 × 1700 |
1210 × 860 × 1950 |
2380 × 860 × 1950 | |||||||
Packing dimension W×D×H (mm) |
900 × 950 × 1950 |
1300 × 950 × 2200 |
1300 × 950 × 2200 (×2) |
1.All models are without internal battery; they should be connected with external battery pack;
2.Custom-made specifications are acceptable;
3.All specification is subject to change without prior notice.